● The measurement of A-type residual current;
● The streamer display of current percentage;
● The setting of rated residual action current;
● The setting of non-driving time of limitation;
● Two-pair relay output;
● Possessing the function of on-the-spot and long-distance testing and resetting
04 Network
Technical Parameter
|
Value |
|
Input |
Rated residual
operated current I△n
|
0.03, 0.05, 0.1, 0.3, 0.5, 1, 3, 5, 10, 30(A) |
Limitation non driving time
|
0,0.06, 0.1, 0.2, 0.3, 0.5, 0.8, 1, 4, 10(S) |
|
Rated non-action residual current
|
50%I△n |
|
Frequency
|
50Hz±5Hz |
|
Tripping accuracy
|
-20% ~ -10%I△n |
|
Output |
Output mode
|
1 normal changeover contact |
Contact capacity |
AL1: 8A 250VAC 5A 30VDC
AL2: 6A 250VAC 5A 30VDC
|
|
Reset mode
|
Local, remote, automatic |
|
Auxiliary power supply
|
Voltage range |
AC/DC85~270V |
Power consumption |
≤5W |
|
Power frequency withstand voltage
|
The effective value of alternating current between the power supply, input and output: 2kV/1min
|