● A complete set of protection, related to the application;
● 3 current input, 3 voltage input, 11DI, 5DO;
● Auxiliary power supply adapts with AC220V, DC220V, DC110V, AC110V, DC48V, DC24V;
● 1 RS485 serial communication, IEC60870-5-103 and Modbus-RTU;
● 1 GPS for GPS timing;
● More than 200 sequence of event records, more than 400 system logs, and more than 10 seconds tripping context records;
● Powerful graphic programmable Logic.
02 LCD Display
04 Typical Connection
Rated Parameter | Power Supply |
Power supply: AC/DC220V,Or AC/DC110V, or DC48V(Reference the wiring diagram) |
Range: Power supply x (1±20%) |
||
Maximum power consumption: ≤10W(DC) |
||
Rated Voltage |
Rated Voltage: AC100V |
|
Range: 1-120V |
||
Accuracy: ±0.5% |
||
Power Consumption: ≤0.5VA(Single phase) |
||
Overload capacity: 1.2 times rated voltage for continous work; 2 times for 10 seconds |
||
Rated Current |
Rated current: AC 5A/1A(See the device wiring diagram) |
|
Range: 0.04In~15In |
||
Power consumption: ≤0.5VA(Single phase) |
||
Over capacity: 2 times rated current for continuous work; 40 times for 1 second |
||
Frequency |
Rated frequency: 50Hz or 60 Hz |
|
Range: 45~55Hz |
||
Accuracy: ±0.1Hz |
||
Digital Inut |
Rated Voltage: AC/DC220V,AC/DC110V, DC48V(Similar to power supply) |
|
Voltage Range: Rated voltage x (1±20%) |
||
Power Consumption: ≤1W(DC220V)(Single channel) |
||
Digital Output |
Mechanical life: ≥10000 times |
|
Switching capacity: ≥1000W, L/R=40ms |
||
On current: continuous≥5A short time(200ms)≥30A |
||
Interrupting capacity: ≥30W, L/R=40ms |
||
Normal Working Conditions |
Ambient temperature: -10℃~+55℃ |
|
Device storage, transport allows the ambient temperature is -25℃~+70℃ |
||
Relative humidity: 5%~95% |
||
Altitude: ≤4000m |