● Current transformer for measurement
● Suitable for cables or busbar
● Used with energy meters or relays

02 Installation


03 Wiring

|
Specification
|
Rated Current Ratio (A)
|
Precision Degree and Corresponding Rated Load (VA/Ω)
|
Straight-through tums
|
Bus Spec(mm)/
Number
|
Installation
|
||
|
0.2
|
0.5
|
1
|
|||||
|
30II
|
100/5(1)
|
|
|
1.5
|
1
|
30x10/1-2
|
A, C
|
|
150/5(1)
|
|
|
1.5
|
1
|
|||
|
200/5(1)
|
|
2.5
|
|
1
|
|||
|
250/5(1)
|
|
3.75
|
|
1
|
|||
|
300-450/5(1)
|
|
5
|
|
1
|
|||
|
500/5(1)
|
|
10
|
|
1
|
|||
|
600/5
|
|
10
|
|
1
|
|||
|
40II
|
100/5(1)
|
|
|
1.5
|
1
|
40×10/1-2
|
A,C
|
|
150/5(1)
|
|
|
2.5
|
1
|
|||
|
200/5(1)
|
|
2.5
|
|
1
|
|||
|
250/5(1)
|
|
3.75
|
|
1
|
|||
|
300-450/5(1)
|
|
5
|
|
1
|
|||
|
500-800/5(1)
|
|
10
|
|
1
|
|||
|
1000/5(1)
|
10
|
|
|
1
|
|||
|
50II
|
150
|
|
|
2.5
|
1
|
50×10/1-2
|
|
|
200-250/5(1)
|
|
2.5
|
|
1
|
|||
|
300-450/5(1)
|
|
5
|
|
1
|
|||
|
500-800/5(1)
|
|
10
|
|
1
|
|||
|
1000-1250/5(1)
|
10
|
|
|
1
|
|||
|
1500/5(1)
|
20
|
|
|
1
|
|||
|
60II
|
200-250/5(1)
|
|
2.5
|
|
1
|
60×10/1-2
|
C
|
|
300-450/5(1)
|
|
5
|
|
1
|
|||
|
500-800/5(1)
|
|
10
|
|
1
|
|||
|
1000-1250/5(1)
|
10
|
|
|
1
|
|||
|
1500-2000/5(1)
|
20
|
|
|
1
|
|||
|
2500/5(1)
|
30
|
|
|
1
|
|||
|
60×50II
|
200-250/5(1)
|
|
2.5
|
|
1
|
60×10/1-3
|
D
|
|
300-450/5(1)
|
|
5
|
|
1
|
|||
|
500-800/5(1)
|
|
10
|
|
1
|
|||
|
1000-1250/5(1)
|
10
|
|
|
1
|
|||
|
1500-2000/5(1)
|
20
|
|
|
1
|
|||
|
2500/5(1)
|
30
|
|
|
1
|
|||
|
80II
|
200-250/5(1)
|
|
2.5
|
|
1
|
80×10/1-2
|
|
|
300-450/5(1)
|
|
5
|
|
1
|
|||
|
500-800/5(1)
|
|
10
|
|
1
|
|||
|
1000-1250/5(1)
|
10
|
|
|
1
|
|||
|
1500-2000/5(1)
|
20
|
|
|
1
|
|||
|
2500-3000/5(1)
|
30
|
|
|
1
|
|||
|
80×50II
|
200-250/5(1)
|
|
2.5
|
|
1
|
80×10/1-3
|
|
|
300-450/5(1)
|
|
5
|
|
1
|
|||
|
500-800/5(1)
|
|
10
|
|
1
|
|||
|
1000-1250/5(1)
|
10
|
|
|
1
|
|||
|
1500-2000/5(1)
|
20
|
|
|
1
|
|||
|
2500-3000/5(1)
|
30
|
|
|
1
|
|||
|
100II
|
300-450/5(1)
|
|
5
|
|
1
|
100×10/1-2
|
|
|
500-800/5(1)
|
|
10
|
|
1
|
|||
|
1000-1250/5(1)
|
10
|
|
|
1
|
|||
|
1500-2000/5(1)
|
20
|
|
|
1
|
|||
|
2500-4000/5(1)
|
30
|
|
|
1
|
|||
|
100×50II
|
300-450/5(1)
|
|
5
|
|
1
|
100×10/1-3
|
|
|
500-800/5(1)
|
|
10
|
|
1
|
|||
|
1000-1250/5(1)
|
10
|
|
|
1
|
|||
|
1500-2000/5(1)
|
20
|
|
|
1
|
|||
|
2500-4000/5(1)
|
30
|
|
|
1
|
|||
|
100×80II
|
600-800/5(1)
|
|
10
|
|
1
|
100×10/1-4
|
|
|
1000-1250/5(1)
|
10
|
|
|
1
|
|||
|
1500-2000/5(1)
|
20
|
|
|
1
|
|||
|
2500-4000/5(1)
|
30
|
|
|
1
|
|||
|
120×50II
|
500-800/5(1)
|
|
10
|
|
1
|
120×10/1-3
|
|
|
1000-1250/5(1)
|
10
|
|
|
1
|
|||
|
1500-2000/5(1)
|
20
|
|
|
1
|
|||
|
2500-5000/5(1)
|
30
|
|
|
1
|
|||
|
130×50II
|
600-800/5(1)
|
|
10
|
|
1
|
125×10/1-3
130×10/1-3
60×10/2-6
|
|
|
1000-1250/5(1)
|
10
|
|
|
1
|
|||
|
1500-2000/5(1)
|
20
|
|
|
1
|
|||
|
2500-5000/5(1)
|
30
|
|
|
1
|
|||
|
120×80II
150×50II
|
1000-1250/5(1)
|
10
|
|
|
1
|
120×10/1-4
|
D
|
|
1500-2000/5(1)
|
20
|
|
|
1
|
|||
|
2500-5000/5(1)
|
30
|
|
|
1
|
|||
|
170×100II
|
1500-2000/5(1)
|
15
|
|
|
1
|
170×10/1-3
100×10/3-6
|
|
|
2500-5000/5(1)
|
30
|
|
|
1
|
|||
|
180×50II
|
1200-2000/5(1)
|
10
|
|
|
1
|
180×10/1-3
|
|
|
2500-5000/5(1)
|
30
|
|
|
1
|
|||
|
200×50II
220×50II
260×50II
|
1500-2000/5(1)
|
20
|
|
|
1
|
200×10/1-3
100×10/4-6
|
|
|
2500-5000/5(1)
|
30
|
|
|
1
|
|||
|
260×100II
|
1200-1500/5(1)
|
10
|
|
|
1
|
250×10/2-5
125×10/4-10
|
|
|
1500-2000/5(1)
|
20
|
|
|
1
|
|||
|
2500-6300/5(1)
|
30
|
|
|
1
|
|||