Precision Distribution Monitoring Solution For IDC

Precision Distribution Monitoring Solution For IDC

May 10, 2022

 
It is necessary to real-time monitor and centralize power consumption in data center and data can be displayed on HMI,and uploaded to the power and environment monitoring system by RS485 on touch screen and realize real-time monitoring of whole power distribution system. At the same time, it can realize energy efficiency analysis to reduce energy consumption. 
 
  •  
  •  
  •  
  •  
  •  
  •  
  •  
  •  
 
1. For the HVDC 240V/336V system, an insulation monitoring module can be configured to monitor the insulation resistance of the positive and negative busbars to ground, ensuring the safe, stable and reliable operation of the system.

2. Both the touch screen and the outgoing monitoring module are powered by DC 24V output from the incoming monitoring module.

3.Incoming line and outgoing line circuits independent monitoring modules

4.Can measure up to 2 incoming line circuits and up to 192 outgoing line circuits current, voltage, power, energy and power quality.

5.Data centralized monitoring and display by HMI and data is uploaded to power and environment monitoring system through RS485.

6.For high voltage DC 240V or 336V system,insulation monitoring module can be added to monitor ground insulation resistance of main bus.

7.DC24V power supply for touch screen and outgoing line monitoring module(power supply from main module output)

8.Communication:monitoring device by RS485,touch screen by RS485 or RJ45

9.Certificate:CE 
 
 

Name

Pic

Model

Main Function

HMI

 

ATP007kt
ATP010kt

1.7 or 10 inch touch screen
2.Real-time monitoring and display voltage,current,power,energy,power quality,switch status,waveform curve and so on.
3.monitoring device alarm,communication and other parameters can be configured on the screen.
4. 2 RS485 and 1 Ethernet interface,and data can be uploaded by RS485 or RJ45

AC incoming line monitoring module

 

AMC16Z-ZA

1. Installation:DIN rail 35mm
2. Measurement:A+B independent 3 phase circuits, 6DI2DO,2 leakage current,1 temp. and humidity.
3. With DC 24V output power supply for outgoing line module and touch screen.
4. Communication:RS485 Modbus RTU

AC outgoing line monitoring module

 

AMC16Z-FAK24
AMC16Z-FAK48

1. Installation:DIN rail 35mm
2. Can measure up to 16 circuit 3 phase or 48 circuit single phase
3. DC24V power supply
4. Communication:RS485 modbus RTU

AC outgoing line current transformer

 

AKH-0.66W

Current ratio:100A/50mA
Common Specification: 100A/50mA

DC incoming line monitoring module

 

AMC16Z-ZD

1. Installation:DIN Rail 35mm
1. Measurement:A+B independent circuits,6DI2DO,1 temp. And humidity.
2. With DC 24V output power supply for outgoing line module and touch screen.
3. Communication:RS485 modbus RTU

DC outgoing line monitoring module

 

AMC16Z-FDK24
AMC16Z-FDK48

1. Installation:DIN Rail 35mm
2. Can measure up to 48 circuits DC outgoing line
3. DC24V power supply
4. Communication:RS485 modbus RTU

DC incoming line insulation monitoring module

 

AMC16Z-ZJY

1. Installation:DIN Rail 35mm
2. Measure A+B independent DC circuit ground insulation resistance of main bus
3. DC24V power supply
4. Communication:RS485 modbus RTU

DC outgoing line insulation monitoring module

 

AMC16Z-FJY

1. Installation:DIN Rail 35mm
2. Measure 24 circuits ground insulation resistance of DC outgoing line

DC outgoing line hall effect current sensor

 

AHKC-BS

 

Current ratio:100A/5V
Common Specification: 100A/5V

 
  •  
  •  
  •  
  •  
 
  •  
  •  
  •  
  •