● 220V (single phase three wire system), 380V (three phase five wire system)
● Rated current: 100A to 630A(configurable as request)
● power distribution extensions


03 Application

| Rated voltage | Rated insulation voltage | 660V | |
| Rated working voltage |
220V (single phase three wire system), 380V (three phase five wire system) |
||
| Rated impact withstand voltage Uimp | 8kV | ||
| Overvoltage class | III | ||
| Pollution levels | Class 2 | ||
| Rated frequency | 50HZ | ||
| Rated current | Rated current | 100A to 630A(configurable as request) | |
| Rated short-time withstand current | 6kA | ||
| EMC Electromagnetic compatibility | Industrial 2 class | ||
| insulation resistance | ≥10MΩ | ||
| dielectric strength | 1min 2500V | ||
| Grounding Resistance | ≤0.1Ω | ||
| structural characteristics | |||
| Size(mm) | width | 600、800、1000 | |
| height | 2000、2200 | ||
| depth | 600、800、1000、1100 | ||
| oscillation specification | 5Hz~50Hz,amplitude 20mm/s | ||
| Cabinet color | RAL9004 | ||
| Surface treatment | Epoxy resins electrostatic powder spraying | ||
| Protection level | IP20 | ||
| Componenets installation in cabinet | Fixed type or plug-in type | ||
| Installation | Floor type | ||
| Installation place | indoor | ||
| Material specifications | frame | RKIII | |
| mounting plate | ALZINC | ||
| Door plank | Mesh or glass doors | ||
| Output switch | 6A~63A(single phase or three phase) | ||
| Output circuit | 21-84 channels | ||
| alarm style | Audible and visual alarm | ||
| Communication port | RS485,RS232 and LAN(ethernet) optional | ||
| Main feeder monitoring parameters |
Three-phase voltage, current, frequency, zero sequence current, active/reactive power, power factor,Active/reactive energy, total harmonic content, 2~15 harmonics, etc |
||
| Main feeder alarm item |
Three phase overvoltage/undervoltage, phase deficiency, imbalance, three phase current overcurrent, zero sequence overcurrent, high/low frequency |
||
| Outgoing circuit | Outgoing voltage, current, load percentage, switch on/off state, etc | ||
| Sub-alarm item | Outgoing circuit overload warning, outgoing open circuit alarm lamp, etc | ||
| Ground/zero connection | Single floor row/zero row | ||
| Feeder and outgoing mode | Up incoming or down incoming | ||
| Two circuits system | Optinal | ||
| Environment | operating temperature | -5℃ to 40℃ | |
| Relative humidity | ≤93%RH(25℃±5℃时) | ||
| altitude | ≤2000m | ||
| storage |
Well ventilated, temperature -25℃ ~ +55℃, relative humidity ≤85%, the surrounding environment does not contain corrosive gas, no harmful chemicals and gases in the warehouse |
||