RS485(Modbus-RTU)
Display
LCD display, set multiplying power
Rated U & I
AC current: AC1A, 5A
Frequency
Range: 45-65Hz
Consumption
Power consumption of each voltage, current input circuit is less than 0.5VA
Accuracy
Class 0.5
Installation
Panel mounted
Dimension(L*W*H)
Panel size (L×W): 75*75mm
Cutout (L×W): 67*67mm
Housing (L×W×H): 66*66*94.3mm
Auxiliary power supply
Voltage range: AC220V
Power consumption: <5VA
Relay
3A/30V DC, 3A/250V AC
|
Technical Parameter
|
Value
|
|
Input
|
Rated Value
|
AC voltage:Single phaseAC 100V,400V Three phaseAC 100V,400V,660V(UL-L,Only 72/ 96) AC current:AC1A,5A; DC voltage:1000V,300V,75mV,10V; DC current: 0-20mA,4-20mA,5A;
|
|
Overload
|
Voltage: 1.2 times rated value(continuous); 2 times rated value /1 second Current:1.2 times rated value(continuous); 10 times rated value /1 second
|
|
Frequency
|
45Hz~65Hz
|
|
Power Consumption
|
Power consumption of each voltage,current input circuit is less than 0.5VA
|
|
Accuracy
|
Class 0.5
|
|
Function
|
Display
|
LED or LCD
|
|
Communication
|
RS485,Modbus-RTU protocol;(1 start bit,8 data bit,1 stop bit,no parity) Baud Rate 2400/4800/9600/19200 bps etc.
|
|
Alarm
|
1 channel passive relay,contact capacity 3A/30VDC,3A/250VAC, Used for high,low,unbalance alarm etc.
|
|
Analog
|
DC4~20mA,( load <500Ω) (note:Shielded wire is specially selected for the above signal input and output)
|
|
Switching
|
Input:4 channel or 2 channel dry contact Input,built in power supply Output:2 channel switching output,NO relay contact,capacity:3A/30VDC,3A/250VAC
|
|
Auxiliary Supply
|
AC/DC 85-265V
|
|
Power Consumption
|
<5VA
|
|
Insulation resistance
|
≥ 100MΩ
|
|
Power frequency withstand voltage
|
Between power supply set of terminals and signal input,output set of terminals 2kV/1min (RMS) Between the shell and all set of terminals(except the set of terminals reference voltage less than 40V) AC 4kV
|
|
Environment
|
Temperature
|
Operation: -10℃~+55℃Storage: -25°C ~+70°C
|
|
Humidity
|
≤95%RH,no condensation,without corrosive gas
|
|
Altitude
|
≤ 2500m
|